| 4-20 mA input | Requires a 500 Ohm resistor and minimum voltage set to 2 V in the input service settings |
|---|---|
| Analog inputs | 0-10 V, measurement range 0-12 VDC, single-ended, 8-bit resolution, accuracy 0.1% of full scale, input impedance > 16 kOhm, normal mode rejection 50 dB at 55 Hz, conversion time 1250 ms |
| Digital inputs | Push button inputs; reed / status inputs |
| Sensor terminals | 2 EXT terminals for relative air humidity sensor and CO2 sensor |
| Universal inputs | 6 |
| Impulse counter inputs | 100 Hz per channel, sample rate 200 Hz per channel, pulse on time > 5 ms |
| NTC temperature inputs | Resistance range 100 Ohm – 100 kOhm ±50 Ohm; deviation on 1 km Cat6 cable: -0.3 °C at 25 °C |